We are in the process of transitioning to a new plan review and inspection database. As a result, the plan review and plan log status reports will change and may not be available for a period of time. Please be patient with us during this transition as we work hard to improve our processes and communication to our customers.

NOTE - THE NOTED DISAPPROVED ITEMS MAY NOT CONSTITUTE A COMPLETE LIST OF VIOLATIONS. THE DESIGNER IS TO CONDUCT A COMPLETE RE-REVIEW OF THE PLANS FOR ADDITIONAL VIOLATIONS OF THE STANDARD COMMENTS AND INCORRECT INFORMATION PRIOR TO RESUBMITTING.

 System plans must be picked up within 30 days. All system plans left longer than 30 days will be discarded as abandoned.

PIKES PEAK PLAZA BUILDING 2
00710 PIKES PEAK AVE

Review DateStatusComment(s)
5/11/2021 FYI*****(STANDARD COMMENT) This project is: Pikes Peak Tower Building 2 710 E Pikes Peak Ave, New Mixed Use Apartment Building Electronic Plan Rapid Response This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT) The fire sprinkler system is being installed by: Frontier Fire Protection CSFD does not allow any combustibles into a building until a sprinkler system has passed it's final acceptance test performed by CSFD Inspector's.
FYI*****ADDITIONAL FEES: This is our --2nd---, review of these plans. Any and all future plan submittals for this specific permit will have additional plan review fees charged to the project, as per the approved fee schedule.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) RTP REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Roland Peterson Senior Fire Inspector, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7369 rpeterson@springsgov.com
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Provide the CSFD plan review number on the plans. REPEATED COMMENT 2. Correct the FDC location to the approved location. REPEATED COMMENT AS A RESULT STANDPIPE HYDRAULICS HAVE NOT BEEN REVIEWED. 3. CPVC in OH area - provide documentation on allowed area is not exceeded. (2019 NFPA 13 16.3.9.3) A maximum area of 400 sq ft for non-light hazard occupancies. The pipe in the storage area is now shown as gray but no pipe legend appears on the plans. 4. Is there interstitial space? THIS MUST BE DECLARED ON THE PLANS OR HEADS PROVIDED. 5. Provide manufacturer's recommended expansion loop size for top three floors. PROVIDED ON PLANS. CORRECT LENGTHS PER MANUFACTURERS CALCULATOR 6. Isolation valve for standpipe. NFPA 14 6.3.2 7. Provide area reduction calculation and code reference. 8. The fire flow provided does not list the hydrant the fire sprinkler system is calculated to. Calculation L1.1 is very tight. Provide a fire flow for the hydrant the calculations terminate at. NO SPRINKLER HYDRAULICS CAN BE REVIEWED. 9. Provide a three snoot FDC not a six snoot. Also review the disapproved plans for additional written comments prior to submittal of new plans.
FYI*****(STANDARD COMMENT) DISAPPROVED ITEMS ADDRESSED: The plans have been resubmitted and all the disapproved comments have been addressed and/or corrected as follows: 1. Is there interstitial space? THIS MUST BE DECLARED ON THE PLANS OR HEADS PROVIDED. 2. Storage walls are shown the same as the corridor walls if this is true then additional coverage is needed. CORRECTED ON PLANS 3. Sidewall heads on some of the balconies do not meet the required distance. CORRECTED 4. Provide manufacturer's recommended expansion loop size for top three floors. PROVIDED ON PLANS. CORRECT LENGTHS PER MANUFACTURERS CALCULATOR 5. Correct side walls for balconies that do not extend to the balconies. CORRECTED 6. Provide stair section as required for NFPA 13 and 14. PROVIDED 7. Provide nodes for riser valves and standpipe on stair riser section. PROVIDED 8. Provide hose valves on the roof. PROVIDED
4/16/2021 FYI*****(STANDARD COMMENT) This project is: Pikes Peak Tower Building 2 710 E Pikes Peak Ave, New Mixed Use Apartment Building Electronic Plan Rapid Response This plan review is based on the requirements found within the adopted Editions of the International Building Code, International Fire Code and the related Standards.
FYI*****(STANDARD COMMENT) The fire sprinkler system is being installed by: Frontier Fire Protection CSFD does not allow any combustibles into a building until a sprinkler system has passed it's final acceptance test performed by CSFD Inspector's.
FYI(STANDARD COMMENT) REVIEWS: Colorado Springs Fire Department construction reviews are based upon information provided on the drawings and/or the attached reference material. Issues or features that are not presented within the construction documents are assumed to be complaint with applicable codes/standards. It is the responsibility of the building owner to ensure that minimum code requirement are met as established by the Authority Having Jurisdiction, whether or not the requirements are specifically indicated on the submitted construction documents. The CSFD has reviewed the submittal in accordance with the fire code requirements of the adopted International Fire Code, CSFD local amendments, City Code Standards, and applicable NFPA Standards. All plan review comments are subject to final on-site field inspections, and testing by the CSFD. Review and approval by the CSFD shall not relieve the applicant of the responsibility of compliance with the International Fire Code. (105.4.4)
FYI(STANDARD COMMENT) RTP REVIEWER CONTACT: If you have any specific questions or concerns about these comments, please feel free to contact me at: Roland Peterson Senior Fire Inspector, CSFD 2880 International Circle, Suite 200-7 Colorado Springs, CO 80910 (T) 719-385-7369 rpeterson@springsgov.com
Disapproved*****(STANDARD COMMENT) DISAPPROVED COMMENTS The following information and/or corrections are needed prior to completing a full plan review. Please respond, in writing on letterhead, to each of the following comments: 1. Provide the CSFD plan review number on the plans. 2. Correct the FDC location to the approved location. 3. CPVC in OH area - provide documentation on allowed area is not exceeded. 4. Is there interstitial space? 5. Storage walls are shown the same as the corridor walls if this is true then additional coverage is needed. 6. Sidewall heads on some of the balconies do not meet the required distance. 7. Provide manufacturer's recommended expansion loop size for top three floors. 8. Correct side walls for balconies that do not extend to the balconies. 9. Hydraulic calculations have not been reviewed due to missing expansion loops. 10. Provide stair section as required for NFPA 13 and 14. 11. Provide nodes for riser valves and standpipe on stair riser section. 12. Provide hose valves on the roof. 13. Hydraulic calculations have not been reviewed. Review stopped. Also review the disapproved plans for additional written comments prior to submittal of new plans.
Attention(STANDARD COMMENT) THE DISAPPROVED ITEMS MAY NOT CONSITITUE A COMPLETE LIST OF VIOLATIONS. It is the responsibility of the design professional to conduct a complete re-review of the plans for additional violations of the adopted codes/standards and incorrect information prior to resubmitting.
FYI(STANDARD COMMENT) CORRECTIONS All corrections and comments are to be submitted back to CSFD in writing, or provide submittal sheets/drawings, etc as requested, to complete the review. Corrections are not accepted over the phone, via fax, email or verbally.
 